Availability: | |
---|---|
HYCB2LE-32 (DPNLE)
CSQ
HYCB2LE-32 (DPNLE) protective circuit breaker is suitable for single-phase residential lines with AC 50Hz or 60Hz and rated voltage of 230V. It is used for leakage protection and overload and short circuit protection of civil electrical lines. This product has a small size. , The breaking capacity is high; the zero and live wires are cut off at the same time, and the leakage can still be protected when the live wire is reversed.
This product conforms to IEC61009-1 and other standards. The filter device in the electronic leakage and overvoltage protection circuit breaker can prevent false tripping caused by instantaneous voltage (lighting, line interference of other equipment) and instantaneous current (such as large capacitive load lines).
Model | HYCB2LE-32 (DPNLE) | ||
Rated Current Ie (A) | 6A-63A | ||
Rated Voltage Ue | 230V | ||
Breaking capacity Icu | 4kA |
Overcurrent trip characteristic table
Test current | Rated voltage | Set time | Expected result | Starting state | Remark |
1.13In | All values | t ≥ 1h | Non-trip | Cold state | The current rises steadily to the specified value within 5s |
1.45In | All values | t < 1h | Trip | Cold state | Close the auxiliary switch to turn on the power |
2.25In | All values | 1<t < 60s | Trip | Cold state | Close the auxiliary switch to turn on the power |
5In | All values | t ≥ 0.1s | Non-trip | Cold state | Close the auxiliary switch to turn on the power |
10In | All values | t < 0.1s | Trip | Cold state | Close the auxiliary switch to turn on the power |
Note: HYCB2LE-32(DPNLE) (phase line + neutral line + leakage current) protects the filter device in the circuit breaker, which can prevent instantaneous voltage (lighting, line interference of other equipment) and instantaneous current (such as large capacitive load lines) ) caused by malfunction tripping.
HYCB2LE-32 (DPNLE) protective circuit breaker is suitable for single-phase residential lines with AC 50Hz or 60Hz and rated voltage of 230V. It is used for leakage protection and overload and short circuit protection of civil electrical lines. This product has a small size. , The breaking capacity is high; the zero and live wires are cut off at the same time, and the leakage can still be protected when the live wire is reversed.
This product conforms to IEC61009-1 and other standards. The filter device in the electronic leakage and overvoltage protection circuit breaker can prevent false tripping caused by instantaneous voltage (lighting, line interference of other equipment) and instantaneous current (such as large capacitive load lines).
Model | HYCB2LE-32 (DPNLE) | ||
Rated Current Ie (A) | 6A-63A | ||
Rated Voltage Ue | 230V | ||
Breaking capacity Icu | 4kA |
Overcurrent trip characteristic table
Test current | Rated voltage | Set time | Expected result | Starting state | Remark |
1.13In | All values | t ≥ 1h | Non-trip | Cold state | The current rises steadily to the specified value within 5s |
1.45In | All values | t < 1h | Trip | Cold state | Close the auxiliary switch to turn on the power |
2.25In | All values | 1<t < 60s | Trip | Cold state | Close the auxiliary switch to turn on the power |
5In | All values | t ≥ 0.1s | Non-trip | Cold state | Close the auxiliary switch to turn on the power |
10In | All values | t < 0.1s | Trip | Cold state | Close the auxiliary switch to turn on the power |
Note: HYCB2LE-32(DPNLE) (phase line + neutral line + leakage current) protects the filter device in the circuit breaker, which can prevent instantaneous voltage (lighting, line interference of other equipment) and instantaneous current (such as large capacitive load lines) ) caused by malfunction tripping.
Hangzhou Office Address:
13th Floor,Building 6, Huacai International, Xihu District, Hangzhou City,China
Wenzhou Factory Address:
No. 198, Wei 3rd Road, Economic Development Zone Of Yueqing, Wenzhou city, China
+86-577-61737670