Model: HYCB2LE-32 (DPNLE)
Breaking Capacity: 4kA
Rated Current: 6A/10A/16A/20A/25A/32A
Rated Voltage: 230V
Standard: IEC60898-1; GB10963.1
Availability:
  • HYCB2LE-32 (DPNLE)

  • CSQ

HYCB2LE-32 (DPNLE) protective circuit breaker is suitable for single-phase residential lines with AC 50Hz or 60Hz and rated voltage of 230V. It is used for leakage protection and overload and short circuit protection of civil electrical lines. This product has a small size. , The breaking capacity is high; the zero and live wires are cut off at the same time, and the leakage can still be protected when the live wire is reversed.

This product conforms to IEC61009-1 and other standards. The filter device in the electronic leakage and overvoltage protection circuit breaker can prevent false tripping caused by instantaneous voltage (lighting, line interference of other equipment) and instantaneous current (such as large capacitive load lines).



Model

HYCB2LE-32 (DPNLE)

Rated Current Ie (A)

6A-63A

Rated Voltage Ue

230V

Breaking capacity Icu

4kA



Overcurrent trip characteristic table

Test currentRated voltageSet timeExpected resultStarting stateRemark
1.13InAll valuest ≥ 1hNon-tripCold stateThe current rises steadily to the specified value within 5s
1.45InAll valuest < 1h
TripCold stateClose the auxiliary switch to turn on the power
2.25InAll values1<t < 60sTripCold stateClose the auxiliary switch to turn on the power
5InAll valuest ≥ 0.1sNon-tripCold stateClose the auxiliary switch to turn on the power
10InAll valuest < 0.1sTripCold stateClose the auxiliary switch to turn on the power

 

Note: HYCB2LE-32(DPNLE) (phase line + neutral line + leakage current) protects the filter device in the circuit breaker, which can prevent instantaneous voltage (lighting, line interference of other equipment) and instantaneous current (such as large capacitive load lines) ) caused by malfunction tripping.


Previous: 
Next: 

QUICK LINKS

PRODUCT CATEGORY

CONTACT US

  Hangzhou Office Address:

13th Floor,Building 6, Huacai International, Xihu District, Hangzhou City,China

  Wenzhou Factory Address: 

No. 198, Wei 3rd Road, Economic Development Zone Of Yueqing, Wenzhou city, China

  +86-577-61737670

  csq@siqi.cc

Leave a Message
Send Message
Copyright  2021 Siqi Technology Co.,Ltd. All Rights Reserved.